DOC
WEC-ART-010
CLASS
Installation · Spacing
TIER
Layer 4
Technical Article · Installation & Maintenance

How to Determine
Cable Cleat Installation Spacing

Published 2026-05-30Read time ~5 minStandard ref. IEC 61914
RELATED
Short-circuit forceSelection paramsInstall mistakes
§ 01
Introduction
§ 02
Three governing factors
§ 03
Spacing–kA relationship
§ 04
Vertical vs. horizontal
§ 05
Calculation workflow
§ 06
Field execution

"Around 1 metre should be fine" is an acceptable approximation for plenty of mechanical engineering problems. For cable cleat spacing on a high-fault-current power circuit, it is an engineering error. Spacing and short-circuit withstand are paired parameters; changing the spacing changes the effective protection level of the installation even if the cleat is unchanged.

§ 01  Three factors that govern maximum spacing

Maximum spacing between adjacent cable cleats is constrained by three independent limits — the most restrictive governs:

  • Short-circuit electromagnetic force — the primary design driver for most power circuits. Longer span → greater cable deflection under the lateral impulse → higher bending moment at each cleat. The manufacturer's type-test report declares the maximum spacing at which the rated kA level is valid;
  • Cable self-weight (vertical runs) — large-section cable can weigh 5–10 kg/m. Over a 100 m vertical drop, the cumulative axial tension on the lowest cleats is significant. For large-conductor vertical runs, self-weight can govern spacing before the fault-force limit is reached;
  • Manufacturer's declared rating — the product datasheet maximum spacing value integrates both considerations and must not be exceeded regardless of engineering judgement.

§ 02  The spacing–kA relationship

This is the most commonly misunderstood aspect of cable cleat selection. A given cleat model does not have a single kA rating — it has a kA rating at a specified installation spacing. Increasing the spacing reduces the effective short-circuit withstand of the installation, even though the cleat body is identical.

Illustrative relationship (logic only — not real product data)

Spacing 500 mm → withstand 63 kA peak
Spacing 750 mm → withstand 40 kA peak
Spacing 1 000 mm → withstand 25 kA peak

Always obtain the actual spacing–kA table from the manufacturer's type-test report for the specific product being specified.

The correct selection sequence is: determine peak fault current iₚ first, then find the maximum spacing that supports that kA level from the test report — not the reverse.

§ 03  Vertical vs. horizontal runs

Vertical runs experience both the lateral short-circuit impulse and the axial self-weight tension simultaneously. For large-section cable on long vertical drops, the self-weight constraint can require spacing considerably tighter than the short-circuit limit alone would suggest. Bottom-section cleats (highest cumulative weight) may need closer spacing than top-section cleats.

Horizontal runs experience the short-circuit lateral force without the axial self-weight component — gravity is perpendicular to the cable axis and is carried by the support structure. Spacing for horizontal runs is governed by the short-circuit limit and can often be somewhat larger than the equivalent vertical-run requirement for the same fault level.

§ 04  Practical calculation workflow

  • Obtain the prospective steady-state fault current Isc (RMS) from the protection coordination study;
  • Calculate peak current iₚ = κ × Isc (use κ = 2.5 for typical HV systems, or derive from X/R ratio);
  • From the manufacturer's test report, find the maximum spacing for which the product's kA rating ≥ iₚ;
  • For vertical runs, additionally check self-weight axial loading against cleat mechanical rating;
  • Record the derived spacing in the installation drawings — it is a design parameter, not a site instruction left to the installer's discretion.
Core principle — Spacing is a design parameter embedded in drawings. Any site deviation from the drawing value requires an engineering justification and written approval, not a field decision. See Installation Mistakes for consequences of over-spacing.
[1]IEC 61914 — kA rating and installation spacing are always declared together in the test report [2]Peak factor κ ≈ 2.5 (conservative); exact value from X/R ratio per IEC 60909 [3]Why spacing affects force: the span–deflection–moment relationship [4]Selection parameters: spacing in the six-parameter framework [5]Over-spacing: the most common installation error