DOC
WEC-ART-007
CLASS
Selection · Hub
TIER
Layer 3
Technical Article · Selection Guide

Cable Cleat Selection:
The Parameters You Cannot Afford to Miss

Published 2026-05-30Read time ~6 minStandard ref. IEC 61914
RELATED
Short-circuit forceMaterialsInstallation spacing
§ 01
Introduction
§ 02
Cable OD
§ 03
Formation
§ 04
kA withstand
§ 05
Material
§ 06
Temperature
§ 07
Spacing
§ 08
Checklist

A common root cause of cable fixing rework: the cleat was ordered based on cable OD and nothing else. It arrived on site, was installed, and passed every visual inspection — then the wrong formation type was flagged in an audit, or the kA rating turned out to be below system peak current. Getting six parameters right simultaneously is the only way to avoid that pattern.

Six core cable cleat selection parameters overview diagram
FIG. 01 · Six core selection parameters — any single gap invalidates the specification

§ 01  ① Cable OD: measure, don't estimate

Every cable cleat has a declared applicable OD range. The actual OD of a cable varies with conductor cross-section, insulation wall, sheath material, and manufacturer tolerances — two cables with the same nominal cross-section from different manufacturers can differ by several millimetres in OD.

Always use the measured or datasheet OD against the cleat's declared range. A cleat that is too loose allows axial slip and lateral displacement during a fault; one that is too tight compresses the sheath and damages insulation over time.

Verification path — Obtain the cable manufacturer's technical datasheet, find the "outer diameter (OD)" row, and check it against the cleat's applicable range before ordering.

§ 02  ② Installation formation: the first fork in the decision tree

Formation determines which cleat type is required:

  • Single-core — half-shell single-cable cleat;
  • Flat (trefoil) three-core multicore — three-hole flat cleat;
  • Trefoil formation (three single-core in equilateral triangle) — dedicated trefoil cleat that holds all three conductors in position simultaneously.

Trefoil formation is not optional for three-phase single-core installations — it is the engineering-correct arrangement. The resultant electromagnetic force in trefoil is substantially lower than in flat formation, and only a proper trefoil cleat locks the geometry to preserve that advantage during a fault. See Trefoil Formation for the full physics.

§ 03  ③ Short-circuit withstand (kA): the most frequently missed parameter

This figure distinguishes a cable cleat from everything else on the market. Electromagnetic force between conductors scales with the square of current. At a 50 kA peak, each metre of cable sustains close to one tonne of lateral impulse. A cleat that has not been tested at that level provides no engineering assurance at that level.

Selection procedure
1. Obtain steady-state prospective fault current Isc (RMS) from the protection study.
2. Apply peak factor κ (conservatively 2.5): iₚ = 2.5 × Isc.
3. Cleat declared kA rating ≥ iₚ — verified by IEC 61914 type test report, not catalogue declaration alone.

§ 04  ④ Material and environment: two constraints in one

Material selection is governed by two independent requirements that must both be satisfied:

Corrosion resistance governs the material family: UV-stabilised nylon (PA66) for sheltered low-corrosion locations; aluminium alloy for onshore medium-corrosion; 316 stainless steel for offshore C5-M environments.

Single-core magnetic constraint adds a hard rule regardless of environment: any cleat encircling a single-core AC cable must be non-magnetic. Ferromagnetic steel forms an induction heating circuit; aluminium alloy, 304/316 austenitic stainless, and engineering nylon are all acceptable. See Cable Cleat Materials.

§ 05  ⑤ Working temperature: the hidden ceiling for polymers

Metallic cleats require no temperature check in most wind turbine installations. Polymer cleats — PA66 nylon — have a declared upper working temperature above which mechanical strength drops sharply.

Locations to check: converter rooms and transformer bays at tower base, where full-load thermal rise can add 40–60 °C; high-ambients in tropical climates; cable runs with sustained high current generating self-heating. If working temperature exceeds the nylon rating, switch to a metallic material.

§ 06  ⑥ Installation spacing: the last tuning variable

Cleat spacing and kA rating are not independent. The manufacturer's declared kA rating applies only at or below the maximum installation spacing stated in the test report. Increasing spacing reduces the effective short-circuit withstand of the installation, even if the cleat body is unchanged.

Spacing is also affected by cable self-weight on vertical runs — large-section cables accumulate significant axial load over long vertical spans. The detailed calculation is in Installation Spacing.

§ 07  Selection checklist

ParameterVerification point
① Cable ODMeasured OD within cleat's declared applicable range?
② FormationSingle / flat multicore / trefoil? Correct cleat type selected?
③ kA withstandPeak current iₚ calculated? Cleat rating ≥ iₚ per test report?
④ MaterialCorrosion category matched? Single-core → non-magnetic confirmed?
⑤ TemperaturePolymer cleats within rated temperature at worst-case location?
⑥ SpacingManufacturer's maximum spacing for this kA level written into drawings?

All six parameters must be satisfied simultaneously. A specification that addresses five out of six is not a partial pass — it is an incomplete specification.

[1]IEC 61914 — kA rating and installation spacing are always declared together [2]Peak factor κ ≈ 2.5 (conservative); exact value from system X/R ratio [3]Short-circuit force: why kA is the decisive parameter [4]Materials: non-magnetic rule for single-core [5]Spacing: kA–spacing relationship explained